FEMA E-74 Example 6.5.1.1 Light Duty Shelving

Main Content

You are here: Table of ContentsChapter 66.5 FF&E and Content Examples: 6.5.1 Storage Racks

6.5.1.1 Light Duty Shelving

Download "6.5.1.1 Light Duty Shelving" (PDF 1MB)

This category includes light duty shelving units and sheet metal storage cabinets. These items are typically tall and narrow and may be heavily loaded.

Provisions

Building Code Provisions

The seismic design requirements of Minimum Design Loads for Buildings and Other Structures (ASCE/SEI 7-10) Chapter 13 are intended to apply only to permanently attached components, not to furnishings, temporary items, or mobile units.  Storage cabinets and shelving units of significant mass are not considered to be exempt and should be anchored or braced.

Permanent floor-supported shelving or storage cabinets over 6 feet tall must be designed as architectural components per ASCE/SEI 7-10.  Bracing and anchorage for these units should be designed considering the weight of the unit and weight of shelved contents.

Retrofit Standard Provisions

Seismic Rehabilitation of Existing Buildings (ASCE/SEI 41-06) classifies light-duty shelving as force controlled, and the principal objective of the code provisions is to prevent the component from sliding or overturning. ASCE/SEI 41-06 requires compliance with the anchorage provisions of the standard for storage racks over 4 feet in height when the performance level is Life Safety or higher.  Storage racks in unoccupied spaces are exempt.

Typical Causes of Damage

  • Shelving units may slide or overturn and the contents may become dislodged or fall. Where there are rows of freestanding or poorly anchored shelves, the failure of a few may result in progressive collapse of many. Broken bottles, spilled chemicals, mixed or damaged inventory are often the result of the failure of storage or display units.
  • Mobile storage carts may roll, overturn, or impact other items. Stored contents may become dislodged or fall.
  • Damage to contents or inventory that has fallen from shelving can be costly to repair or replace and may result in substantial business interruption.

Damage Examples

Photo of collapsed shelving units.
Figure 6.5.1.1-1 Collapse of row of unanchored freestanding shelving units containing spare parts at an electric power plant in Port-au-Prince in the 2010 magnitude-7 Haiti Earthquake (Photo courtesy of Eduardo Fierro, BFP Engineers).

Photo of floor showing a nine inch scratch caused by unanchored storage shelving which slid.
Figure 6.5.1.1-2 Unanchored storage shelving slid nine inches without falling but contents scattered in the 2001 magnitude-8.4 Peru earthquake; unit lifted to original position prior to photo (Photo courtesy of Eduardo Fierro, BFP Engineers).

Seismic Mitigation Considerations

  • For sheet metal cabinets or shelving, anchor units to floor, tie back-to-back units together, strap rows of units together across the top, or anchor units to an adjacent wall. Light duty steel storage racks may additionally require cross bracing.
  • See Section 6.5.6.1 for recommendations regarding edge restraints and arrangement of shelf-mounted items. Do not locate cabinets or racks adjacent to doors or exits if their failure would block the exit.
  • Any connections to stud walls must engage the structural studs. Stud walls and partitions may not have adequate lateral capacity to support many shelving units; engineering may be required. Where items are anchored to heavy partitions, the bracing or anchorage of these partitions to the structure above must also be checked for adequacy considering the seismic loads imposed by all anchored items.
  • The details shown are intended for light duty units; heavy duty units with large loads may require engineering. See Seismic Considerations for Steel Storage Racks Located in Areas Accessible to the Public (FEMA 460) for additional information on the performance of industrial storage racks. Some racks are available with enhanced seismic performance; check other resources, such as the internet for additional options.

Mitigation Examples

Photo of seismic mitigation example showing mobile carts restrained at base with clip angles.
Figure 6.5.1.1-3 Mobile carts restrained at base with clip angles anchored to the floor and removable eyebolts attached from each cart to the angles (Photo courtesy of Maryann Phipps, Estructure).

Photo of seismic mitigation example showing restraint at base of mobile shelving unit.
Figure 6.5.1.1-4 Alternate restraint at base of mobile shelving unit (Photo courtesy of Maryann Phipps, Estructure).

Photo of seismic mitigation example showing 
shelving units anchored at base with seismic base plate offered by manufacturer.
Figure 6.5.1.1-5 Fixed base shelving units anchored with optional seismic base plate offered by manufacturer (Photo courtesy of Maryann Phipps, Estructure).

Photo of seismic mitigation example showing restraint at base of mobile shelving unit.
Figure 6.5.1.1-6 Mobile cart restrained at base with removable angles and eyebolts. Back-to-back units are interconnected (Photo courtesy of Maryann Phipps, Estructure).

Photo of seismic mitigation example showing fixed base shelving units anchored directly to concrete slab through base plate.
Figure 6.5.1.1-7 Fixed base shelving units anchored directly to concrete slab through base plate (Photo courtesy of Maryann Phipps, Estructure).

Photo of seismic mitigation example showing mobile shelving unit restrained by connection to strut fastened to full height metal studs and seismic mitigation example detail showing connection to strut.
Figure 6.5.1.1-8 Mobile shelving unit restrained by connection to strut fastened to full height metal studs (Photo courtesy of Maryann Phipps, Estructure).

Mitigation Details

Seismic mitigation example showing shelving units anchored at base with seismic base plate offered by manufacturer. Consult an appropriate professional for implementation.
Figure 6.5.1.1-9 Light Duty Shelving (NE, ER).

Back | Table of Contents | Next